低压配电柜的操作规程方法
低压配电柜的操作规程方法:
Operation rules and procedures of low voltage distribution cabinet:
1.低压配电柜的操作人员需通过国家相关部门培训、考核并获得进网证和操作证。
1. the operators of low voltage switchboard should be trained and
evaluated by relevant departments of the state, and get the net card and
operation certificate.
2.低压配电柜的操作人员熟悉本岗位规章制度和变配电设备的性能、操作方法以及事故情况下的正确处理方法。
2. operators of low-voltage distribution cabinet are familiar with the
rules and regulations of this station, the performance of power
distribution equipment, the operation methods and the correct handling
methods in case of accidents.
3.熟悉并正确使用电工安全用具和消防用具。
3. 、 familiar with and correct use of electrical safety appliances and
fire appliances.
4.配电房维修必须挂相关警示牌,二人进行,一人操作,一人监护,巡检时可以一人进行,但必须通知其它当班人员,与被检设备保持0.7米以处距离。
4., distribution room maintenance must hang relevant warning signs, two
people, one person operation, one person custody, patrol can be carried
out by one person, but must inform other duty personnel, and the
equipment to keep 0.7 meters distance.
2、检查
2, check
1.柜门开关动作灵活可靠,屋顶无渗漏水,柜外、柜内清洁无杂物,柜门钥匙、操作棒、警示牌等齐全。
1.. The door switch is flexible and reliable. The roof is free of
seepage and water. The cabinet is clean with no sundries. The cabinet
keys, operating rods and warning signs are complete.
2.各负荷开关手自动合闸分闸灵活可靠,过压、过流、欠压、失压保护功能完好,安装接线牢固可靠无灼痕,隔离开关合闸分闸灵活可靠,安装牢固,触点(连接处)接触牢固、无灼痕。
2. load switch hand automatic closing gate is flexible and reliable,
overvoltage, overcurrent, undervoltage, voltage loss protection function
intact, firm and reliable installation wiring without burning,
isolation and switching operations is flexible and reliable, firm
installation, contact (connection) contact firmly without burning.
3.各面板指示灯齐全,指示仪表(含互感器)指示准确且在有效期内使用。
3. the panel indicator lamp is complete, indicating instrument
(including transformer) indicating accurate and within the validity
period.
4.补偿电容无漏液,功率补偿仪工作正常指示准确。
4., compensation capacitor without leakage, power compensation device
work properly, accurate instructions.
5.接地线油漆无脱落,紧固螺丝牢固,接线线或排无破损、硬伤、腐蚀现象。
5. ground paint off, firm fastening screws, wire or row without damage,
flawed, corrosion phenomenon.